Manual Balancing Commercial Control Industrial Control
Light Duty Medium Duty Industrial Duty
Fire Dampers Fire/Smoke Dampers Smoke Dampers
Extruded Aluminum Formed Metal/Steel Combination/Operable Acoustical Sight Screens/Penthouses

Formed Metal/Steel Louvers

Free Area Based on 48x48 Unit Water Penetration Ratings Based on 48x48 Unit Wind Driven Rain Ratings Based on 39x39 Unit Product Sheet CSI Specification Installation Instructions Revit Files
Model Frame Depth Blade Angle Type Blade Style SQFT Percent Velocity (fpm) Air Volume (cfm) Pressure Loss (inwg) Wind Class Effectiveness Ratio Rainfall Rate Wind Speed Core Velocity(fpm) Airflow(cfm) AMCA CRP Listing
SFD-445 4" 45 Steel Drainable D 8.5 53% 715 6,092 0.11 - - - - - - - PDF Doc PDF RFA
SFD-635 6" 35 Steel Drainable D 9.9 62% 815 8,044 0.08 - - - - - - - PDF Doc PDF RFA
SFJ-245 2" 45 Steel Thinline J 6.7 42% 603 4,040 0.06 - - - - - - - PDF Doc PDF RFA
SFJ-430 4" 30 Steel J 8.2 51% 847 6,945 0.13 - - - - - - - PDF Doc PDF RFA
SFJ-445 4" 45 Steel J 7.7 48% 775 5,991 0.13 - - - - - - - PDF Doc PDF RFA
SFJ-630 6" 30 Steel J 10.4 65% 825 8,580 0.08 - - - - - - - PDF Doc PDF RFA
SFJ-645 6" 45 Steel J 8 50% 800 6,400 0.09 - - - - - - - PDF Doc PDF RFA
SFK-445 4" 45 Steel K 7.7 48% 775 5,991 0.13 - - - - - - - PDF Doc PDF RFA
SFK-645 6" 45 Steel K 8 50% 800 6,400 0.09 - - - - - - - PDF Doc PDF RFA
SFV-445 4" 45 Steel Sightproof Chevron 6.1 38% 600 3,648 0.25 - - - - - - - PDF Doc PDF RFA

Click on header to sort the results