3 Hour - Static Fire Damper
Curtain Style Blade
The VFD-30-A fire damper employs curtain style blades for point-of-origin control of fire in static HVAC systems. The VFD-30-A may be installed in vertical walls or partitions, or horizontally in floors or assemblies with fire resistance ratings up to 4 hours.
Frame: 22 ga. (0.85) galvanized steel.
Blades: 24 ga. (0.7) galvanized steel - curtain style.
Fire Closure Device: Fusible link.
Fire Closure Temperature: 165oF (75oC)
Minimum Size:
Vertical Mount: 4" x 4" (102 x 102)
Horizontal Mount: 6" x 10" (152 x 2542)
Maximum Size:
Single Section:
Vertical: 36" x 36" (915 x 915)
Horizontal: 38" x 36" (965 x 915)
Multiple Section:
Vertical: 108" x 24" (3048 x 1930)
Horizontal: 76" x 96" (1931 x 2438)
Stainless Steel:
Single Section:
Vertical: 36" x 24" (914 x 610)
Multiple Section:
Vertical: 108" x 24" (2743 x 610)
UL 555 Fire Resistance Rating: 3 hour (vertical and horizontal)
UL HNLJ.V-5: Ventilation Duct Assemblies